HENGFENGYOU ELECTRIC --SMART ELECTRIC GLOBAL SERVICE PROVIDER
   

Low Voltage Power Cable

VV Low Voltage Power Cable

  • Brand: HENGFENGYOU
  • Series: VV
  • USES: Power Transmission
  • Country of origin: China
  • Terms of payment: L/C, T/T, Western Union, Paypal, Money Gram
  • Certification: ISO9001、CE

PVC insulated power cable with rated voltage of 0.6/1kv (non armored)
Product introduction
Scope of application
This product is applicable to AC 50Hz transmission and distribution lines with rated voltage of 0.6/1kv.
Executive standard
Gb/t 12706-2008 extruded insulated power cables and accessories with rated voltages from 1kV to 35kV
Flame retardant and fire-resistant cables shall also meet gb/t19666-2005 general rules for flame retardant and fire-resistant wires and cables
Model and specification
Model: vv
Name: copper core PVC insulated PVC sheathed power cable
Nominal sectional area mm ²: 1.5-300 (1-5 cores)
Model: VLV
Name: aluminum core PVC insulated PVC sheathed power cable
Nominal sectional area mm ²: 1.5-300 (1-5 cores)
Model: Z (a, B, C, d) -vv
Name: copper core PVC insulated PVC sheathed flame retardant power cable
Nominal sectional area mm ²: 1.5-300 (1-5 cores)
Model: Z (a, B, C, d) -vlv
Name: aluminum core PVC insulated PVC sheathed flame retardant power cable
Nominal sectional area mm ²: 1.5-300 (1-5 cores)
Model: Z (a, B, C, d) n-vv
Name: copper core PVC insulated PVC sheathed flame retardant fire resistant power cable
Nominal sectional area mm ²: 1.5-300 (1-5 cores)
Guidelines for use
Rated voltage uo/u:0.6/1kv;
Long term allowable working temperature: the long-term working temperature of the conductor shall not exceed 70 ℃, and the maximum working temperature during short circuit shall not exceed 250 ℃ (the maximum duration shall not exceed 5S);
The cable laying temperature shall not be lower than 0 ℃;
Minimum bending radius (D is the outer diameter of the cable)
Single core cable: 20d;
Multi core cable: 15d.
Special characteristics
Flame retardant products: the flame retardant characteristics meet the requirements of gb/t 19666-2005 general rules for flame retardant and fire resistant wires and cables;
Flame retardant and fire-resistant products: flame retardant and fire-resistant characteristics meet the requirements of gb/t 19666-2005 general rules for flame retardant and fire-resistant wires and cables.


Previous:VV22 Low Voltage Power Cable Next:No article

News and information

Contact us

WhatsApp:

+86 15853252696(Jack)

+86 158 5326 5269(Alisa)

Tel:+86-532-87936206

Fax:+86-532-87936207

Email: hfy@hengfengyou.com

Address: No.638,Zhongcheng Road, Chengyang District, Qingdao City,China

Leave a message now - get the latest industry insights, star products, and success stories of hengfengyou electric

Click to replace Click to replace

© 2021 Copyright By Hengfengyou Electric

xml map    |    Site map

whatsapp
(+86) 15853252696
WhatsApp Click Contact